Inverted Bucket Steam Trap

Condensers should be installed in an easily accessible position and on the ground for maintenance. The differential pressure on the product label must be greater than the differential pressure value of the system. The kondestop should be mounted horizontally, so that the bucket will move more or less vertically . The connection of the horizontal condensers will be horizontal, the connection of the vertical condenser will be vertical, but its input will be below. The condensate should be installed below the discharge level, so that water sealing can be ensured around the bucket.

1. Install the condenser on the underside of the equipment that will drain the condensate and close to the equipment. Avoid having a horizontal long pipeline in front of the condenser.
2. In order to prevent potential ram impact problems, all horizontal lines should be inclined downwards towards the condenser.
3. In all models, a dirt holder should be installed in front of the condenser .
4. When the condensate needs to be disassembled for testing or other purposes, the gland and the shut-off valve should be installed on both sides of the condensate during installation in order to make the disassembly operation easy.
5. A test and discharge valve should be installed to relieve the internal pressure before maintenance.
6. If the return line is pressurized or the condenser is draining upwards, a check valve should be placed on the return line.

Reverse bucket condensers may need to be filled with water before they are put into operation. For this, any of the following methods is used.

1. The pipe plug on the condenser cover is removed and water is filled in until it is completely filled, and the pipe plug is closed.
2. The return line valve is kept closed until the condensate is completely filled with condensate, then slowly opened.

CARE 
The condensate should be inspected and cleaned periodically. Worn parts should be replaced with a new one.

SPARE PARTS
No Explanation Material
1 BONNET GG25
2 BODY GG25
3 VALVE STAINLESS STEEL
4 VALVE SITE STAINLESS STEEL
5 ARM STAINLESS STEEL
6 KOVA KLÄ°PSÄ° STAINLESS STEEL
7 KOVA STAINLESS STEEL
8 FERRULE STAINLESS STEEL
9 FILTER GASKET KLINGERIT
10 VALVE CLIP STAINLESS STEEL
11 INNER TUBE STEEL PIPE
12 PACKING WASHER STAINLESS STEEL + GRAPHITE
13 COVER PLUG STEEL
14 PLUG STEEL
15 PACKING WASHER KLINGERIT
16 COVER BOLT SAE Gr.5
FORM OF CONNECTION FLANGED
DIAMETERS DN15 DN20 DN25 DN30 DN40 DN50
WEIGHTS (Kg) 5,5 6,4 8,1 9,9 15,8 24,9
WORKING CONDITIONS
MAX. TEST PRESSURE (BAR) 24
MAX. TEMPERATURE (ºC) 220
MAX. DIFFERENTIAL PRESSURE (BAR) 5,5-8
MAX. WORKING PRESSURE (BAR) 16

1683182447447-e1686681304792

it was founded on 03.01.2023 in Gaziantep. Engineering solutions for steam, fire, water systems.

Contact

  • Beylerbeyi, 84027 Nolu Sokak No:11/G, 27000 Åžehitkamil/Gaziantep

  • info@zenteknik.com

  • +90 342 502 58 91

  • +90 552 881 97 27

© 2024 Zen Teknik Engineering Tüm Hakları Saklıdır. | Gizlilik Politikası

Web Design Digital Küre

Message
To Contact
Zen Teknik
Hello 👋
How Can We Help You?